Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T17CM08302
Parcel: 13605247C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM08302
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2017 TWEIDEM1 BUILDING-RESIDENTIAL REVIEW Reqs Change T17CM08302
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All construction materials and components require notation without the use of colors. Archived records are black and white copies of original drawings.

FLOOR PLANS:

1. Provide the names of adjacent rooms to the new construction for verifying compliance with R310 providing egress from bedrooms. The room addition may not eliminate required egress openings. CLARIFY FLOOR PLAN LAYOUT TO CLARIFY EGRESS POINT, MOVING WALLS MAY BE OPTION.

SECTIONS - DETAILS:

1. Show a cross-section detail of the new exterior wall,
R106 1.1.

2. Notate and specify the size, spacing and length of any (porch) ledger fasteners, R403.1.6.


ELECTRICAL PLANS:

1. Tucson Electric Power requires the utility meter to be relocated from under patio roofs, TEP SR-405.10.L. ADD NOTES TO PLAN FROM TEP DISCUSSION/LETTER.

2. Show receptacle outlets at wall spaces 2' or more with no wall point (exclude door openings) more than 6' from a receptacle outlet, E3901.2.

3. Protect all new and extended interior 15A & 20A proposed outlets (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12. WILL CLARIFY.


If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/30/2017 QJONES1 APPROVAL SHELF Completed
11/30/2017 QJONES1 OUT TO CUSTOMER Completed
11/30/2017 QJONES1 REJECT SHELF Completed