Permit Number: T17CM08302
Parcel: 13605247C

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T17CM08302
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2017 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T17CM08302
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All construction materials and components require notation without the use of colors. Archived records are black and white copies of original drawings.

FOUNDATION PLANS:

1. Provide a exterior wall detail showing a 6" minimum separation of exterior siding or sheathing above finished grade, R317.1 item 5. Also, show the weep screed with a minimum clearance 4" above grade or 2" above paved areas, R703.6.2.1. This may require a design with concrete stems.

FLOOR PLANS:

1. Provide the names of adjacent rooms to the new construction for verifying compliance with R310 providing egress from bedrooms. The room addition may not eliminate required egress openings.

SECTIONS - DETAILS:

1. Show a cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12" footing depth below the undisturbed ground surface (R403.1) with 12" minimum width for wood framed walls R403.1.1. Show exterior wood siding, sheathing and wall framing with a 6" clearance above the ground (R317.1 item 5) with minimum ½" diameter anchor bolt and treated sill plates, R602.10.8 & R403.1.6.
2. Notate and specify the size, spacing and length of any (porch) ledger fasteners, R403.1.6.
3. Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.
4. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray or rigid board tight to the roof sheathing), R806.5. This condensation control provision is necessary for code compliance, and may be a single layer of air-impermeable insulation, or layered with batt insulation for achieving the total required roof R-value.

ELECTRICAL PLANS:

1. Tucson Electric Power requires the utility meter to be relocated from under patio roofs, TEP SR-405.10.L.
2. Show receptacle outlets at wall spaces 2' or more with no wall point (exclude door openings) more than 6' from a receptacle outlet, E3901.2.
3. Show at least one wall-switch-controlled lighting outlet providing illumination on the exterior side of each egress door having grade level access R3903.3.
4. Protect all new and extended interior 15A & 20A proposed outlets (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12.
5. Provide notation requiring tamper resistant receptacles for 125 volt, 15A and 20A receptacles, R4002.14.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Show the maximum "U" factors of the windows and doors on the plans as well as the solar heat gain coefficient SHGC minimum value of 0.25, N1102.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/29/2017 KROBLES1 OUT TO CUSTOMER Completed