Permit Number: T17CM08247
Parcel: 117050890

Address:
340 N 4TH AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM08247
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/06/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/06/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
11/06/2017 ROBERT SHERRY WATER REVIEW Completed
11/06/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet a3.0; Project Data (Occupancy): Is the B occupancy correct for this use? Sheet a3.0 indicates dining rooms and a kitchen. Please verify and revise as required.
2. Sheet a3.0; Project Data (Code Review): This sheet indicates the health code is not applicable. Please verify if this restaurant does not require that review.
3. Sheet a3.0; Floor Plan Keynotes: Note 1 indicates a new interior metal stud wall. Please provide a detail on the drawing indicating how the top of the wall is braced (to roof deck/by diagonal braces), including bracing size and connections as required.
4. Sheet a3.0; Floor Plan Keynotes: Note 4 indicates to 'provide new panic hardware if none existing'. This is noted at two separate doors. Please remove the 'if none existing., and verify if it is existing (one is a new door).
5. General: The drawings we looked at do not match the drawings for this permit. The east portion is not indicated to be part of the west portion is not indicated to be part of the west portion. Two permits for the east portion (T14CM03543 and T16CM09364) were withdrawn for work in this area, and a demolition permit was also withdrawn in 2014. No drawings we saw had the east and west portions combined. Please review the history of this space and clarify.
6. General: Please provide written responses to all review comments.
11/06/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/07/2017 MARTIN BROWN FIRE REVIEW Approved
11/07/2017 DAVID RIVERA ZONING REVIEW Reqs Change IID required for change of use from take-out to sitdown restaurant.
11/15/2017 KROBLES1 ENGINEERING REVIEW Needs Review