Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM08179
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/01/2017 | KELLY LEE | ZONING | REVIEW | Approved | |
| 11/01/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide ventilation calculations. 2. Provide exhaust for the restrooms and for the beauty salon. 3. An air balance report will be required prior to the mechanical final inspection. |
| 11/01/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide specifications for the new water closet, the new lavatory, the water heater, and the dishwasher. 2. Provide tempered water for both lavatories using a mixing valve listed to ASSE 1070. 3. Verify the the maximum developed length of the hot water piping from the water heater to the furthest outlet is less than 50-feet. 4. Provide a detail of the water heater installation. 5. Provide drinking fountain or point-of-use- water dispenser. |
| 11/01/2017 | KLEE1 | ENGINEERING | REVIEW | Passed | |
| 11/01/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/01/2017 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Verify the size of the water meter - Tucson Water records show a 5/8" meter for this address. 2. Verify the presence of a reduced pressure backflow preventer for this addres (it is not included in the water pressure calculations). |
| 11/01/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/01/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/13/2017 | ARUIZ1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |