Permit Number: T17CM08138
Parcel: 11307003A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM08138
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2017 MGAYOSS1 ZONING REVIEW Approved
10/31/2017 TPROBAS1 MECHANICAL-COMMERCIAL REVIEW Completed
10/31/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a maintenance receptacle for the mechanical equipment as required per NEC art, 210.70C.
10/31/2017 MGAYOSS1 ENGINEERING REVIEW Passed
10/31/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Structural Calculations; Sheet C1: Please include a structural drawing (full size) of the existing roof framing and the new RTU's. Sheet C1 indicates to keep all mechanical loads off the 8"x8" beams. Where are these beams located? Indicate on the plan.
2. Structural Calculations; Sheet C2: Where are these 2x8 at 24" o.c. located? Indicate on the plan.
3. Structural Calculations; Sheet C3: Where are these 6"x6" beams located? Indicate on the plan.
4. Structural Calculations; Sheets D1 and D2: Please indicate the detail cuts on the roof framing plan. Provide the details (shown in the calculations) on that sheet.
10/31/2017 TPROBAS1 WATER REVIEW Completed
10/31/2017 TPROBAS1 PLUMBING-COMMERCIAL REVIEW Completed
10/31/2017 MARTIN BROWN FIRE REVIEW Approved
10/31/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed