Permit Number: T17CM08137
Parcel: 113070060

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T17CM08137
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide structural calculations for the new heat pumps being placed on the roof. Revise the roof framing plan as required.
03/22/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref: Plan Sheet E3.0. Indicate conduit, conductor sizes and types for the feeder between panel A and B.
#2. Designate and assign an OCPD for panel B.
Ref: 2012 IBC 107.2.1, 2011 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
04/11/2018 LPEREZ2 OUT TO CUSTOMER Completed