Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T17CM08137
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/22/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide structural calculations for the new heat pumps being placed on the roof. Revise the roof framing plan as required. |
| 03/22/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref: Plan Sheet E3.0. Indicate conduit, conductor sizes and types for the feeder between panel A and B. #2. Designate and assign an OCPD for panel B. Ref: 2012 IBC 107.2.1, 2011 NEC |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/11/2018 | LPEREZ2 | OUT TO CUSTOMER | Completed |