Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T17CM08084
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/11/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; The 2012 Tucson/Pima County Outdoor Lighting Code. (OLC) (a) The lighting plan E2.1 shows 4 under canopy luminaires Keyed Note #23. Provide a Mark on this plan sheet that correlates with the luminaire schedule and the Outdoor Lumen calcs. (b) Plan Sheet ES1.1 shows 2 flagpole luminaires and Plan Sheet E2.1 only shows 1. Please clarify. (c) Ref; Plan Sheet ES2.1. Provide a note on the plan whether or not a special inspection for the outdoor lighting is required. (OLC) sec 104.2.2, 106.2.1. (d) Provide compliance with section 403.1 and 403.5 (Curfew Requirements) for the unshielded exterior luminaires 'OJ' up-lighting. Ref; 2012 IBC 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code. |
| 12/18/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 12/18/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/18/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |