Permit Number: T17CM08084
Parcel: 13705494B

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T17CM08084
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2018 ELISA HAMBLIN ZONING REVIEW Approved
12/06/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Verify that the HVAC system can accomodate the latent and sensible loads from the dishwasher.
12/06/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/06/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the minimum flowing water pressure is 45 PSI or greater at the dishwasher.
2. Provide a tempering kit for the dishwasher drain.
3. Verify the the incoming water temperature mets the manufacturer's requirements (55-75 degrees Fahrenheit).
12/06/2018 EHAMBLI1 ENGINEERING REVIEW Passed
12/06/2018 KROBLES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/06/2018 KROBLES1 OUT TO CUSTOMER Completed