Review Details: REVISION - - 3RD
Permit Number - T17CM08084
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/27/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Designate a panel and branch circuit for the lighting and fans, also show wiring methods. #2. Provide full compliance with the Tucson/Pima County Outdoor Lighting Code. #3. Provide updated panel schedules. #4. ADDITIONAL DISHWASHER REVIEW IS OK TO APPROVE. Ref; 2012 IBC sec 107.2.1, 2011 NEC art 408.4, Tucson/Pima County Outdoor Lighting Code. |