Permit Number: T17CM08084
Parcel: 13705494B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM08084
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2018 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Approved
01/26/2018 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change T17CM08084 – PLAN REVIEW COMMENTS – 3rd review
Reviewer: Chris Anderson, January 25, 2018
MECHANICAL – COMMERCIAL
Regarding ME’s 1/5/18 response to previous mechanical comments 1and 2: while make-up air is required, bringing air in through the RTU’s appears to require that the RTU’s be oversized. The capacities of the RTU’s shall not be in excess of the calculated cooling loads (except minimal overage necessitated by the incremental capacities of available units) to comply with the 2012 IECC C402.2.
01/31/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera for Steve Shields Principal Planner
PDSD Zoning Review Section
PROJECT: T17CM08084 (Related to DP17-0081)
Chic-Fil-A - Restaurant, 1188 West Irvington Road - Lot 4
Building Plan (3rd Review)

TRANSMITTAL DATE: January 31, 2018

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.
2. Until the all other PDSD review agencies have approved the building plans zoning cannot approve the building plans.
3. Remove the unapproved version of the DP17-0081 from the building set or mark them as "for reference only". If including a copy of the DP in the building set, it must be the approved and signed version.
4. The remaining comments from the Mechanical plans reviewer do not appear to be major and will not affect any zoning review purview requirements. Zoning is willing to do an over the counter review and approval of the building plans with an appointment or as a walkthrough.
If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields any time during the week at (520) 837-4956 or email Steve.Shields@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
02/16/2018 QJONES1 APPROVAL SHELF Completed
02/16/2018 QJONES1 OUT TO CUSTOMER Completed
02/16/2018 QJONES1 REJECT SHELF Completed