Permit Number: T17CM08084
Parcel: 13705494B

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T17CM08084
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2017 MARTIN BROWN FIRE REVIEW Approved
10/30/2017 ROBERT SHERRY WATER REVIEW Reqs Change Detail 4/P-6.1 shows a reduced pressure backflow preventer for the water service to the building installed in the storage room. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. See also sheet 12 of 12 (Utility Plan) in the civil drawings for coordination. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf

WATER – COMMERCIAL
Provide water calculations to verify water meter and water service line sizes. Ref. 2012 IPC 106.3.1.
10/31/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
Provide outdoor lumen calculations for the developed area per the 2012 City of Tucson/Pima County Outdoor Lighting Code Table 401.1. The Photometric Plan on sheet ES2.1 does not provide the information required. Include in the calculations all existing exterior lighting (if any) and new exterior lighting in the developed area for this project. The developed area will be the 1.37 acres indicated on the development plan, sheet 1, and the lighting area is “E3.”
The maximum color temperature allowed for exterior lighting is 3500K per Outdoor Lighting Code 402.1. Revise the Luminaire Schedules on sheets ES2.1 and E1.1 to comply.
10/31/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
All text in these document shall be minimum 3/32” high, both upper and lower case. Text included on sheet GD1 does not comply and is unreadable.
Provide water and sanitary fixture calculation tables for the entire facility, including fixtures supplied by the kitchen contractor. Ref. 2012 IPC 106.3.1.
Provide grease interceptor sizing calculations per City of Tucson amendment to the 2012 IPC 1003.3.4.1 to confirm that the specified 1500 gallon tank is justified. Over sizing of grease interceptor can cause odor problems.
Beverage dispensers to be directly connected to the potable water supply that do not have integral backflow preventers or air gaps require backflow prevention. Specify the type of backflow prevention device required for each water connection. Ref. 2012 IPC 608.1 and 608.16.1.
10/31/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM08084 – PLAN REVIEW COMMENTS
Reviewer: Chris Anderson, October 27, 2017
BUILDING – COMMERCIAL
The architect’s and engineers’ seals on each sheet must bear the expiration date per Rules of the Board of Technical Registration as found in the Arizona Administrative Code.
The engineer’s seal on the structural calculations must bear the expiration date per Rules of the Board of Technical Registration as found in the Arizona Administrative Code.
In the Development Plan submittal, sheet 11 of 12, there is a patio wall shown at the outdoor seating area, however I can find no elevation or detail for it in the drawing set. Is the “Typical Aluminum Guardrail” shown in detail 5/A-1.1C this wall? If so, please reference this detail on architectural sheet A-1.1B. Ref. 2012 IBC 107.2.1.
On sheet T-1.1, the boxed note on the left side of the sheet indicates R-18.5 ceiling insulation. However the envelope COMcheck requires R-20 insulation. Please revise. Ref. 2012 IBC 107.2.1.
There is a detail marker 6/A-4.1 on each building elevation, sheets A-2.1 and A-2.2. This detail does not exist on sheet A-4.1. Ref. 2012 IBC 107.2.1.
There is a detail marker 8/A-4.1 on each building elevation, sheets A-2.1 and A-2.2. This detail is for a stone veneered exterior wall; however the elevations show stucco in these locations. Provide a stucco base detail, keeping in mind that the stucco weep screed must be located at or below the foundation plate line and minimum 2” above paved surfaces and 4” above ground surfaces. A concrete or cmu foundation curb may be required to achieve this clearance. Ref. 2012 IBC 2512.1.2.
There is a detail marker 6/A3.1 on building elevations 1 and 2/A-2.2 that does not exist on sheet A-3.1. Ref. 2012 IBC 107.2.1.
Detail 3-A4.1 shows 2x4 exterior wall studs with R-13 insulation. Per COMcheck, the insulation must be minimum R-19. Ref. 2012 IBC 107.2.1.
At least half of the west wall of this building is to be constructed with steel studs. Please revise the envelope COMcheck to include this exterior wall assembly and rerun the program.
On sheet SP-8.1 the maximum required U-factor and SHGC for aluminum entrances and storefronts in specification Section C08411, 2.1(G)(1 & 2) is different from what is shown in the glass schedule, sheet A-1.3A, and the building envelope COMcheck. Revise specification to match COMcheck.
The geotechnical report, Terracon #63165064, is marked “DRAFT” on all sheets. Submit the final version of this report sealed by the geotechnical engineer.
There is a reference to detail 12/S3.2 for column C6 baseplate in the Column Schedule, sheet S1.1; however this detail does not exist on sheet S3.2. Ref. 2012 IBC 107.2.1.
For post H2 in the Shearwall Holdown Schedule, sheet S1.1, there is a reference to detail 16/S3.1. Is this a correct reference? The detail does not appear to apply. Ref. 2012 IBC 107.2.1.
General Notes 6 & 7, sheet A-1.1A, in regards to the non-combustible west wall indicated cement board sheathing to retain non-combustibility. However, detail 6A/S3.1 references ½” plywood sheathing. Per 2012 IMC 507.9 materials for this wall must be non-combustible. This exception to this paragraph allows ½” gypsum wallboard as part of the wall assembly.
10/31/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – COMMERCIAL
Submit heating and cooling load calculations summary sheets for the new RTU’s. Load calculations and selection criteria for the heating and cooling equipment shall be based on a summer db outdoor air temperature of 104-degrees F per City of Tucson amendment to the 2012 IECC. The summer (cooling) design temperature to which the RTU’s in the Gas Fired Rooftop Unit Schedule, sheet M-3.1, is stated as 95-degrees F. Comply with the 2012 IECC C403.2.2 for sizing equipment.
Provide outdoor air calculations per 2012 IMC 403.3.
All text in these document shall be minimum 3/32” high, both upper and lower case. Text included on sheet MH-1.1 does not comply and is unreadable.
Type I kitchen hoods fan operation shall be interlocked with cooking appliances and with mechanical makeup air system. Ref. 2012 IMC 507.2.1.1 and 508.1. I do not see where this requirement is located in the drawings for either cooking equipment or mechanical air systems.
The grease duct system for Type I hoods is to be designed and installed to provide maximum 500 feet per minute air velocity within the system. Submit calculations showing that the 8” x 8” and 8” x 9” grease ducts shown in Hood Elevations 3/M-2.1 are designed to meet this requirement.
11/13/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Chic-Fil-A
T17CM08084
Building Plan (1st Review)

TRANSMITTAL DATE: November 13, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The provided development package sheets, DP17-0081, either need to be the approved and signed sheets, marked for reference only, or removed from the building plans.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
11/14/2017 LOREN MAKUS ENGINEERING REVIEW Approved
12/19/2017 ARUIZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/19/2017 ARUIZ1 OUT TO CUSTOMER Completed