Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM08076
Parcel: 114490590

Address:
2450 N AILEEN AV

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T17CM08076
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2017 TWEIDEM1 BUILDING-RESIDENTIAL REVIEW Reqs Change T17CM08076
2450 N. AILEEN AVE.


Plan review for the above referenced structure is completed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code, 2012 International Fire Code, 2011 National Electrical Code and Arizona Revised Statutes. All features have been checked to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

1. Show the sum of the main and backfeed breakers not exceeding 120% of the busbar (and FEEDER conductor) rating, 2011 NEC 690.64 & 705.12 (D). This code requirement limits the amount of generated current applied to both the bus and feeder conductor placed between the two protective devices. Therefore, when backfeeding a loadcenter without a main breaker the feeder between the main breaker and load center bus must be sized as a bus with a minimum rating of (30A + 20A)/1.2. Consider the load center feeder as an extended bus of the load center.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review