Permit Number: T17CM07988
Parcel: 11717023E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07988
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2017 MMORENO1 ZONING REVIEW Approved
10/24/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the nature of the area of work. The architect has labeled it as a "warm shell" and as an exercise room.
2. If the room is to be an exercise room, revise the ventilation calculations.
3. Provide cooling/heating load calculations for the new water source heat pumps
10/24/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/24/2017 MMORENO1 ENGINEERING REVIEW Passed
10/24/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet g2.0; Code Analysis: The cover sheet indicates this is a 'warm shell'. Sheet g2.0 indicates an occupancy classification and an occupant load. Remove these from Sheet g2.0. This information will be required for the tenant improvement permit.
2. Sheet a1.0; Wall Types: Please indicate how the top and bottom of the new partitions are connected to the floor and the structure above.
3. Sheet s2.0; Framing Plan: Please provide structural calculations for the new mechanical supports (see details 1 and 2 on Sheet s1.0).
4. General: Provide a special inspection certificate for field welding and expansion anchors.
5. General: Please provide written responses to all review comments.
10/24/2017 ROBERT SHERRY WATER REVIEW Completed
10/24/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/24/2017 MARTIN BROWN FIRE REVIEW Approved
10/24/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed