Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM07901
Parcel: 11808094P

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM07901
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2017 TPROBAS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/28/2017 TPROBAS1 BUILDING-COMMERCIAL REVIEW Completed
11/29/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Submit a COMcheck Envelope Compliance Certificate for the building alterations. Show the U-values, SHGF, and R-values of all of the components used for COMcheck on the drawings (doors, windows, walls, and roof). [Initial comment: Demonstrate energy code compliance for the alterations to the building envelope based on the current code (e.g. new fenestration and new exterior walls). Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012.]
11/29/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Provide a natural gas schematic showing the both the new and existing gas loads and the developed lengths of the piping. Reference: Section 107.2.1, IBC 2012.]
2. Provide a 3" floor drain, not a 2" floor drain. [Initial comment: Provide a floor drain to drain the entire floor area of the laundry room. The minimum size for the floor drain shall be 3". Reference; Section 412.4, IPC 2012.
12/08/2017 QJONES1 ENGINEERING REVIEW Needs Review
12/08/2017 QJONES1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2017 QJONES1 APPROVAL SHELF Completed
12/08/2017 QJONES1 OUT TO CUSTOMER Completed
12/08/2017 QJONES1 REJECT SHELF Completed