Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM07901
Parcel: 11808094P

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07901
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2017 ROBERT SHERRY WATER REVIEW Completed
10/19/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the ventilation notes on sheet m201. All of the notes refer to a dining room (of varying floor areas) with operable doors and windows but the architectural drawings do not list any dining rooms and all of the windows are fixed. Reference: Section 107.2.1, IBC 2012.
2. Provide make up air for the two dryers. Reference: Section 504.5, IMC 2012.
3. Demonstrate energy code compliance for the alterations to the building envelope based on the current code (e.g. new fenestration and new exterior walls). Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012.
10/19/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a natural gas schematic showing the both the new and existing gas loads and the developed lengths of the piping. Reference: Section 107.2.1, IBC 2012.
2. Provide a floor drain to drain the entire floor area of the laundry room. The minimum size for the floor drain shall be 3". Reference; Section 412.4, IPC 2012.
11/28/2017 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/28/2017 KROBLES1 ELECTRICAL-COMMERCIAL REVIEW Approved PER TOD
11/28/2017 KROBLES1 ENGINEERING REVIEW Needs Review
11/28/2017 KROBLES1 BUILDING-COMMERCIAL REVIEW Needs Review TOD REVIEWED
11/28/2017 KROBLES1 FIRE REVIEW Needs Review
11/28/2017 DAVID RIVERA ZONING REVIEW Approved