Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM07901
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a natural gas schematic showing the both the new and existing gas loads and the developed lengths of the piping. Reference: Section 107.2.1, IBC 2012. 2. Provide a floor drain to drain the entire floor area of the laundry room. The minimum size for the floor drain shall be 3". Reference; Section 412.4, IPC 2012. |
| 10/19/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the ventilation notes on sheet m201. All of the notes refer to a dining room (of varying floor areas) with operable doors and windows but the architectural drawings do not list any dining rooms and all of the windows are fixed. Reference: Section 107.2.1, IBC 2012. 2. Provide make up air for the two dryers. Reference: Section 504.5, IMC 2012. 3. Demonstrate energy code compliance for the alterations to the building envelope based on the current code (e.g. new fenestration and new exterior walls). Reference: Sections C101.4.3, C101.5, C103.2, C303, and C401.2.1, International Energy Conservation Code 2012. |
| 10/19/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/28/2017 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 11/28/2017 | KROBLES1 | ENGINEERING | REVIEW | Needs Review | |
| 11/28/2017 | KROBLES1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | PER TOD |
| 11/28/2017 | KROBLES1 | FIRE | REVIEW | Needs Review | |
| 11/28/2017 | KROBLES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | TOD REVIEWED |
| 11/28/2017 | KROBLES1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |