Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1.0; General Structural Notes (Foundations): Note 1 indicates a soil report was used for the foundation design. Please provide one copy of that report for review.
2. Sheet S3.0; Sections 1, 2, and 3: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the detail references at the top of the columns with an 'A' or 'B' note.
3. Sheet S4.0; Detail 101: The added note references the top 2'-6" of the footing, while the detail indicates 2'-9". Please coordinate.
4. Sheet S4.0; Spread Footing Schedule: Please remove footings from this schedule that were not used in this project.
5. Sheet S4.1; Details 201, 203, and 204: Detail 203 is cut on Detail 201, where a kicker brace is indicated (but not shown on Detail 203), and Detail 204 is cut on Detail 201, where no kicker brace is indicated (but shown on Detail 204). Please coordinate.
6. General: Please provide written responses to all review comments.
11/08/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved