Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM07848
Parcel: 14118618A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07848
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2017 MGAYOSS1 ZONING REVIEW Approved
10/18/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The shell building being modified in this activity was not conditioned. Section C101.4.5, IECC 2012 requires the space to be brought into full compliance with the current energy code. Provide energy code compliance calculations for this suite of the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of this suite of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
2. Show how one of the "Additional Efficiency Package Options" (C406, IECC 2012) is to be accomplished. Reference: Section C401.2, IECC 2012.
3. Review the submitted heating/cooling load calculations and compare them to the proposed capacities of the rooftop units being installed. The capacities of the units are not to be greater than the calculated loads. Reference: Section C403.2.2, IECC 2012.
10/18/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/18/2017 MGAYOSS1 ENGINEERING REVIEW Passed
10/18/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/18/2017 ROBERT SHERRY WATER REVIEW Completed
10/18/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/18/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/19/2017 JVINCEN1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2017 QJONES1 APPROVAL SHELF Completed
10/25/2017 QJONES1 OUT TO CUSTOMER Completed
10/25/2017 QJONES1 REJECT SHELF Completed