Permit Number: T17CM07847
Parcel: 14118618A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07847
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2017 MGAYOSS1 ZONING REVIEW Approved
10/18/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The shell building being modified in this activity was not conditioned. Section C101.4.5, IECC 2012 requires the space to be brought into full compliance with the current energy code. Provide energy code compliance calculations for this suite of the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of this suite of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
2. Show how one of the "Additional Efficiency Package Options" (C406, IECC 2012) is to be accomplished. Reference: Section C401.2, IECC 2012.
3. Review the submitted heating/cooling load calculations and compare them to the proposed capacities of the rooftop units being installed. The capacities of the units are not to be greater than the calculated loads. Reference: Section C403.2.2, IECC 2012.
4. Provide exhaust for the dressing rooms. Reference: Section 403.3, IMC 2012.
5. Revise the mechanical design for AC-4 as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012.
10/18/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change The Mechanical review comments will require additional electrical design for exhaust fan operation. Please coordinate with mechanical.
10/18/2017 MGAYOSS1 ENGINEERING REVIEW Passed
10/18/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A2.0; Enlarged Floor Plan: The wall schedule indicates W1. This wall type was not located on the plan. Please verify.
2. Sheet A2.0; Elevation 4: The end of the horizontal grab bar is indicated as 4'-10" from the back wall. This does not match the side wall dimensions. Please coordinate.
10/18/2017 ROBERT SHERRY WATER REVIEW Completed
10/18/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/18/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/19/2017 JVINCEN1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2017 QJONES1 APPROVAL SHELF Completed
10/25/2017 QJONES1 OUT TO CUSTOMER Completed
10/25/2017 QJONES1 REJECT SHELF Completed