Permit Number: T17CM07814
Parcel: 10922005L

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T17CM07814
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2017 MARTIN BROWN FIRE REVIEW Approved
11/13/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets 1 through 3; Contech Engineered Solutions LLC Bridge Drawings: Please provide two sets of the sealed/signed/dated structural calculations for the bridge design.
2. General; Contech Engineered Solutions LLC: The Arizona State Board of Technical Registration requires the design professional sign the seal on all documents, and include the date the document was sealed. In addition, a notation shall be placed beneath the seal that provides the day, month, and year of the expiration of the current registration. Please provide all as required.
3. Sheets 1 through 2; Contech Engineered Solutions LLC Abutment Drawings: Please provide two sets of the sealed/signed/dated structural calculations for the abutment design.
4. Sheet S1.1; Structural Notes: It is noted that a geotechnical report was used for the foundation design. Please provide one copy of that report for review.
5. Sheets S1.1 through S1.3; Oliden Engineering Radius Arch Drawings: Please provide two sets of the sealed/signed/dated structural calculations for the arch design.
6. Sheets 1 through 4; Contech Engineered Solutions LLC Radius Arch Drawings: Please provide a seal, signature, and dates on all drawings.
7. Drawings Number 3 and Number 6; Retaining Wall Drawings: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise as required.
8. General; All: Please provide a special inspection certificate (available on the City of Tucson website) for all categories of special inspections required, and the name of each special inspector for the specific categories.
9. General: Please provide written responses to all review comments.
11/17/2017 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/29/2017 KROBLES1 OUT TO CUSTOMER Completed