Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM07737
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/13/2017 | MMORENO1 | ZONING | REVIEW | Approved | |
| 10/13/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 10/13/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. See https://www.tucsonaz.gov/pdsd/building-codes for local plumbing code amendments. 2. Revise detail1/P3.0 to provide three independent indirect drains for the 3-compartment sink terminating in an indirect waste reciever. 3. Install the grease interceptor per the manufacturer's instructions (i.e. the flow control device is not to be installed before the indirect waste reciever). 4. Provide a sign for each hand sink stating that no food preparation or utensil washing is to be done in the hand sinks (see the local amentments). |
| 10/13/2017 | MMORENO1 | ENGINEERING | REVIEW | Passed | |
| 10/13/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G100; Code Information: The occupancy type is listed as business (B). This should be a retail (M) use. Please revise and adjust the plumbing fixture requirements and occupant load as required. 2. Sheet A100; Wall Types 1 and 2: Please provide the size of the partition braces. In addition, indicate the connector size and quantity for the connection of the brace to the structure above and to the top of the partition. 3. Sheets D100, EQ100, and A100; Floor Plans: Please add north arrows to the plans. 4. Sheet A100; Key Notes: Note 1 indicates demising wall. That is the wall that will provide the 1 hour fire resistance rating. Please revise the note. 5. Sheet A102; Code Information: Pleasr revise this note per note 1 above. 6. Sheet A400; Soffit Detail: Please revise the angle brace note to include brace size. In addition, provide the connector size and quantity. 7. General: Please provide written responses to all review comments. |
| 10/13/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/13/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/13/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/03/2017 | KROBLES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |