Permit Number: T17CM07720
Parcel: 140420760

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07720
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2017 ALEXANDRA HINES ZONING REVIEW Approved
10/12/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The cooling load calculations indicate a heat pump with less cooling capacity is needed. Verify the load calculations and the size of the specified heat pump.
2. Provide an economizer for the heat pump.
10/12/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/12/2017 AHINES2 ENGINEERING REVIEW Passed
10/12/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A0.0; Code Analysis Data: The occupancy indicates 528 + 96 = 622 total occupancy. This total should be 624, which agrees with the occupant break down on Sheet A0.1. Please revise the 622 total.
2. Sheet A2.0; Proposed Floor Plan 3: Floor plan keynote 1 indicates a new 3 5/8" metal stud partition. Please provide the metal stud gauge in the note.
3. Sheet A3.0; Detail 4: Please indicate the brace stud gauge, and indicate the size and quantity of connectors at the existing roof and at the top of the new partition.
4. General: Please provide written responses to all review comments.
10/12/2017 ROBERT SHERRY WATER REVIEW Completed
10/12/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/12/2017 MARTIN BROWN FIRE REVIEW Approved
10/12/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed