Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM07714
Parcel: 125112440

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07714
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide for arc fault protection in the branch circuits being modified or extended. NEC 210.12b.
#2. Unit 'C' shows ceiling fans with no marking (existing or new) or switching. Also there are no smoke detectors shown. Please clarify.
#3. Designate a branch circuit and panel for the new devices and extended circuits. Also show the panel locations on the floor plans.
Ref; 2012 IBC sec 107.2.1, 2011 NEC art 210.12b, 408.4, City of Tucson Commercial Plan Submittal Requirements. (www.tucsonaz.gov/pdsd).