Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/24/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide for arc fault protection in the branch circuits being modified or extended. NEC 210.12b. #2. Unit 'C' shows ceiling fans with no marking (existing or new) or switching. Also there are no smoke detectors shown. Please clarify. #3. Designate a branch circuit and panel for the new devices and extended circuits. Also show the panel locations on the floor plans. Ref; 2012 IBC sec 107.2.1, 2011 NEC art 210.12b, 408.4, City of Tucson Commercial Plan Submittal Requirements. (www.tucsonaz.gov/pdsd). |