Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM07682
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/11/2017 | KELLY LEE | ZONING | REVIEW | Approved | |
10/11/2017 | TPROBAS1 | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
10/11/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/11/2017 | KLEE1 | ENGINEERING | REVIEW | Passed | |
10/11/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A.1; Floor Plan: Per the IBC Section 1015, two exits are required for the 76 occupant load. Per the IBC Section 1014.2, egress shall not pass through kitchens. Please verify. 2. Sheet A.1; Floor Plan: Is there no demolition required, or no new partitions added, on this project? Please verify. 3. General: Please provide written responses to all review comments. |
10/11/2017 | TPROBAS1 | WATER | REVIEW | Passed | |
10/11/2017 | TPROBAS1 | PLUMBING-COMMERCIAL | REVIEW | Completed | |
10/11/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
10/11/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/12/2017 | QJONES1 | APPROVAL SHELF | Completed |
10/12/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
10/12/2017 | QJONES1 | REJECT SHELF | Completed |