Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM07651
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/10/2017 | MCASTRO2 | ZONING | REVIEW | Approved | |
| 10/10/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the ventilation calculations: identify the spaces used in the calculations (e.g. retail, beauty salon, etc.) 2. Show how the mechanical design complies with item #3 of Section 403.2.1, IMC 2012 (see footnote b of Table 403.3, IMC 2012). |
| 10/10/2017 | MCASTRO2 | ENGINEERING | REVIEW | Passed | |
| 10/10/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/10/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/10/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1.Provide a detail for the water heater showing the valves, expansion tank, and T&P relief. 2. Provide a thermostatic mixing valve for the lavatory that conforms to ASSE 1070 and show how it is to be plumbed. Note: the specified mixing valve is not listed to ASSE 1070. |
| 10/10/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 10/10/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/10/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |