Permit Number: T17CM07651
Parcel: 11451137D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07651
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2017 MCASTRO2 ZONING REVIEW Approved
10/10/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the ventilation calculations: identify the spaces used in the calculations (e.g. retail, beauty salon, etc.)
2. Show how the mechanical design complies with item #3 of Section 403.2.1, IMC 2012 (see footnote b of Table 403.3, IMC 2012).
10/10/2017 MCASTRO2 ENGINEERING REVIEW Passed
10/10/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/10/2017 MARTIN BROWN FIRE REVIEW Approved
10/10/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1.Provide a detail for the water heater showing the valves, expansion tank, and T&P relief.
2. Provide a thermostatic mixing valve for the lavatory that conforms to ASSE 1070 and show how it is to be plumbed. Note: the specified mixing valve is not listed to ASSE 1070.
10/10/2017 ROBERT SHERRY WATER REVIEW Completed
10/10/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/10/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed