Permit Number: T17CM07595
Parcel: 105110460

Address:
4690 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM07595
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change As requested per the plan review comment (c) 10/24/17..."Equipment grounds are not shown with the feeders from the new 48" x 48" x 48" manhole #1 to the existing SES 'MS1' and MS2' as required per NEC art 250.32b.". Please verify equipment grounds are included with the feeders revise the plan to reflect this..
Ref 2012 IBC sec 107.2.1, 2011 NEC.
Dan.santacruz@tucsonaz.gov
11/15/2017 KROBLES1 ZONING REVIEW Needs Review
11/15/2017 KROBLES1 ENGINEERING REVIEW Needs Review