Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T17CM07595
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/06/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/09/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Plan sheet E1.1 shows an existing generator to remain. Plan sheet E6.1 shows a new generator. Are there going to be two generators utilized? Please clarify. #2. The total number of conduits and conductors for all the paralleled feeders do not correlate. Please clarify. See descriptions of feeders on Plan Sheet E6.1. #3. The existing services MS1 and MS2 will no longer be considered service equipment after the installation of the New 'SESA'. Provide for the isolation of the neutrals and grounds per NEC 250.6B, 250.24. #4. Ref: Plan Sheet E6.1. The new 4000 amp transfer switch also shows it as "Utility Generator", please clarify. Ref: 2012 IBC sec 107.2.1, 2011 NEC |
| 10/09/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/24/2017 | QJONES1 | ENGINEERING | REVIEW | Needs Review | |
| 10/24/2017 | QJONES1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/24/2017 | QJONES1 | APPROVAL SHELF | Completed |
| 10/24/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 10/24/2017 | QJONES1 | REJECT SHELF | Completed |