Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM07526
Parcel: 11005318J

Address:
3001 N SWAN RD

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM07526
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2017 MARTIN BROWN FIRE REVIEW Reqs Change Only one exit can be designated as the "main" exit and is permitted to utilize the sign "This door to remain unlocked while building is occupied". The other exit requires panic hardware. Please pick one door as your main exit and revise plans accordingly.
11/30/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The submitted drawings do not call for the installation of a tempering kit or other method to reduce the temperature of the drain water to less than 140 degrees Fahrenheit. [Initial comment: Verify that the discharge from the dishwasher (kitchen equipment number 15186) will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012.]
11/30/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Section 507.2.2, IMC 2012 stipulates that general exhaust is required for any cooking appliances that are not located under a Type II hood. [Initial comment: Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.2.2, IMC 2012.]
12/08/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/19/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
The Comcheck for the interior lighting or calcs for compliance with Ashrae 90.1 could not be located in the construction documents or plans, as stated per the last plan review response letter.
Ref; 2012 IBC sec 107.2.1, 2012 IECC
12/20/2017 DAVID RIVERA ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: David Rivera
PDSD Zoning Review Section
PROJECT: Starbucks Coffee - 3001 N. Swan
T17CM07526
Building Plan (2nd Review)

TRANSMITTAL DATE: December 20, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The approved DP was not available for review and comparison with the revised building plans. The previous comment made by Steve Shields could not be verified if the changes were made as noted in his last review comments. Zoning will review the building plans on the next submittal and assuming the approved dp is available do a comparison for consistency.

The site details shown on sheet G-004 do not match what is shown on development package DP17-0080 and need to be removed from the plans

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956