Permit Number: T17CM07526
Parcel: 11005318J

Address:
3001 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07526
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the plumbing specifications to include the 3/8" Type L copper tubing shown on the plumbing plan on sheet P1101. Reference: Section 308, IPC 2012.
2. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the metering cycle will last for at least 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. At a minimum, beverage dispensers (e.g. tea and coffee makers) require the use of a backflow preventer listed to ASSE 1022. Reference: Section 608.16.10, IPC 2012.
4. Verify that the discharge from the dish washer (kitchen equipment number 15186) will be 140 degrees Fahrenheit or less. Reference: Section701.7, IPC 2012.
5. Revise the calculation for the size of the grease interceptor to include all of the plumbing fixtures that will be discharging to the grease waste system. Clarify the size of the selected unit (50 GPM shown on sheet P1102 and 75 GPM on sheet P1105). Reference: section 1003.3, IPC as amended by the City of Tucson.
6. Provide a vent downstream of the gravity grease separator to protect the seal for the grease separator. Reference: Section 1003.9, IPC 2012.
10/05/2017 ROBERT SHERRY WATER REVIEW Completed
10/05/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
2. Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.2.2, IMC 2012.
3. Verify that the three HVAC systems have controls that are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy (i.e. start time is not just "30-minutes before opening"). Reference: Section C403.2.4.3.3, IECC 2012.
10/10/2017 MARTIN BROWN FIRE REVIEW Reqs Change Please clearly indicate on plans location(s) of panic hardware.
10/17/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G-001; Site Information/Occupancy: The occupant load indicates 67 total for the building, while the seating summary indicates 68 seats. Please coordinate. In addition, add the occupant load for the employees/staff per the IBC Table 1004.1.2.
2. Sheet G-001; Code Information: Please add the 2009 Edition of the ICC/ANSI A117.1 for accessibility.
3. Sheet G-001; Sheet Index: Please indicate G-001 in the index.
4. Sheet G-002; Composite Plan: Please include a calculation on this sheet for the number of accessible seats required per the IBC Section 1108.2.9.1.
5. Sheet G-002; Composite Plan: This plan cuts off the door on the south wall of the building and does not indicate that door as an exit for the kitchen staff. Please include.
6. Sheet G-005; Occupant Load Analysis Plan: Please include a note for the outdoor patio occupant load. In addition, the area of the patio should be included in the total building area per the IBC Section 2 (area) and Section 1004.
7. Sheet G-007; Keynotes: Please revise the last keynote to 21.
8. Sheet G-008; Enlarged Drive-Thru Detail 1: The enlarged detail on the right references 7/G-008. Please revise that reference.
9. Sheets G-011 through G-013: The City of Tucson requires all lettering (upper and lower case) to a minimum of 3/32" in height. Please revise these sheets.
10. Sheet I-114; Keynotes: Note 9 was not located on the plan. Please verify.
11. Sheet I-411; Elevation 8: The water closet is not shown. Please verify.
12. Sheet I-411; Elevation 10: The lavatory is not shown. Please verify.
13. Sheet I-411; Elevations 5 and 8: The vertical grab bar is not shown. Please verify.
14. Sheet I-411; Elevation 7: The lavatory is not shown. Please verify.
15. General: The registered professional of record is required to indicate on his seal the date the drawing was signed. Please include.
16. General: Please provide written responses to all review comments.
10/27/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response. Provide complete compliance with the 2012 IECC for lighting.
10/31/2017 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Starbucks Coffee - 3001 N. Swan
T17CM07526
Building Plan (1st Review)

TRANSMITTAL DATE: October 31, 2017

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The site details shown on sheet G-004 do not match what is shown on development package DP17-0080 and need to be removed from the plans

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956