Permit Number: T17CM07499
Parcel: 109224450

Address:
5590 E RIVER RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T17CM07499
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/30/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/19/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1.0 (Foundation Plan): Structural Calculations (Roof Framing Key Plan): The calculations indicate to use a footing F3 at the west end of B1A. Should this be the west end of B1? Should the F-2 footing at that location be an F-3 per the calculations? Please verify.
2. Sheet S1.0 (Foundation Plan); Structural Calculations (Roof Framing Key Plan): Please provide the calculations for the column at the east end of B1A and the west end of B1.
3. Sheets S1.0 and S2.0; Plans: Are the intermediate beam sizes, support column sizes, and footing sizes the only changes to these two plans? Please verify.
4. Sheet S1.0; Foundation Plan: Did the shear wall sizes or hold downs change from the original design? Please verify.
5. Sheet S2.0; Roof Framing Plan: In the upper roof framing plan (west), a beam B3 is indicated (where Section 6/A4.2 is cut). Looking at that section, where does that B3 occur? Please verify.
6. General: Please provide two sets of calculations signed, sealed, and dated by the engineer of record.
7. General: Please provide written responses to all review comments.

Reviewed by Eric Newcomb
Contact at 520-837-4911 or Eric.Newcomb@tucsonaz.gov
02/26/2019 QJONES1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2019 QJONES1 APPROVAL SHELF Completed
02/26/2019 QJONES1 OUT TO CUSTOMER Completed
02/26/2019 QJONES1 REJECT SHELF Completed