Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM07499
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/13/2017 | QJONES1 | ENGINEERING | REVIEW | Needs Review | |
| 11/13/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 11/13/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. [Initial comment: Provide the civil utility drawings referenced on sheet P1.0 that show the construction of the building sewer and the water service to the building. Reference: Section 107.2.1, IBC 2012.] |
| 11/13/2017 | QJONES1 | ZONING | REVIEW | Needs Review | |
| 11/13/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not resolved. Are the three heat pumps being installed? If they are being installed, provide heating and cooling load calculations to justify the unit capacities. The COMcheck Mechanical Compliance Certificate notes that reduced lighting power density will be used to comply with the requirements of Section C406, IECC 2012. How will the future tenants know this requirement exists? [Initial comment: Clarify the status of the heat pumps shown on sheet M1.0. If they are to be installed as part of the shell construction, provide calculations to show that the building complies with the requirements of the 2012 International Energy Conservation Code for new buildings. Reference: Section C401.2, IECC 2012.] |
| 11/20/2017 | QJONES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/20/2017 | QJONES1 | APPROVAL SHELF | Completed |
| 11/20/2017 | QJONES1 | OUT TO CUSTOMER | Completed |
| 11/20/2017 | QJONES1 | REJECT SHELF | Completed |