Permit Number: T17CM07425
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07425
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2017 KELLY LEE ZONING REVIEW Approved
09/29/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide 400 CFM of exhaust for the barber shop area - only 225 CFM of exhaust is shown. The exhaust flow rates for the restroom and the storage room will not count towards the required exhaust for the barber shop.
09/29/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/29/2017 KLEE1 ENGINEERING REVIEW Passed
09/29/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A11; Floor Plan: Should the wall type W4 on the north wall of the storage room be a rated wall? Please verify and indicate a U.L. Design number as required.
2. Sheet A71; Interior Elevation: Should the bottom elevation be identified as D1/A71? Please verify.
3. General: Please provide written responses to all review comments.
09/29/2017 ROBERT SHERRY WATER REVIEW Completed
09/29/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide a 4" cleanout for the section of 4" horizontal drain upstream of the connecton of P-2 (or change that section of pipe to 3").
09/29/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/02/2017 MARTIN BROWN FIRE REVIEW Approved