Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T17CM07425
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/29/2017 | KELLY LEE | ZONING | REVIEW | Approved | |
09/29/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide 400 CFM of exhaust for the barber shop area - only 225 CFM of exhaust is shown. The exhaust flow rates for the restroom and the storage room will not count towards the required exhaust for the barber shop. |
09/29/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
09/29/2017 | KLEE1 | ENGINEERING | REVIEW | Passed | |
09/29/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A11; Floor Plan: Should the wall type W4 on the north wall of the storage room be a rated wall? Please verify and indicate a U.L. Design number as required. 2. Sheet A71; Interior Elevation: Should the bottom elevation be identified as D1/A71? Please verify. 3. General: Please provide written responses to all review comments. |
09/29/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
09/29/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide a 4" cleanout for the section of 4" horizontal drain upstream of the connecton of P-2 (or change that section of pipe to 3"). |
09/29/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/02/2017 | MARTIN BROWN | FIRE | REVIEW | Approved |