Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM07415
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/23/2017 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/23/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Comment not addressed. [Initial comment: Provide information regarding the custom powder hood (e.g. recirculating or exhaust). Reference: Section 107.2.1, IBC 2012.] |
10/23/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 4; Sheet A1.1; Floor Plan: Note 22.01 has been changed to Note 11.06, but that note has not been added to the Keyed Notes list. Please add. 2. Previous Comment 5; Sheet A2.1; Elevation A2: The hot water heater is indicated on a raised platform. The structural calculations have been provided for the platform, but the framing needs to be shown on the full size drawings. Please add. 3. General: Please provide written responses to all review comments. |
10/23/2017 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
10/25/2017 | KROBLES1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | 1. Calculations have been provided for support of the water heater but no design has been shown on the drawings. [Initial comment: Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2012.] 2. Verify that the manufacturer's listing allows the installation of an expansion tank on the hot water supply piping. [Initial comment: Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503, 504, 606.1, and 607.3, IPC 2012.] 3. No cleanout has been shown for the section of the building drain located immediately downstream of the hydromechanical grease interceptor. [Initial comment: Provide a cleanout for the section of the building drain located immediately downstream of the hydromechanical grease interceptor. Reference: Section 708.3.1 and 708.3.3, IPC 2012.] 4. The specified hydromechanical grease interceptor (Schier GB-25) has a built-in flow control device. The additional flow control fitting and vent shown in the grease interceptor piping detail is not needed. |