Permit Number: T17CM07396
Parcel: 12510020B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07396
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
09/27/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Specify the exhaust fan shown in the new storage room. Include the required airflow for the fan (e.g. 100 CFM @ 0.5" WG). State how the fan is to be controled.
09/27/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/27/2017 MARTIN BROWN FIRE REVIEW Reqs Change Can not exit from a lower hazard through a higher hazard. Please recalculate travel distance from southeast corner of building to legal exit.
09/27/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change Written comments to architect.
09/27/2017 ROBERT SHERRY WATER REVIEW Completed
09/27/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide secondary roof drainage.
10/03/2017 QJONES1 ENGINEERING REVIEW Needs Review
10/03/2017 QJONES1 ZONING REVIEW Needs Review