| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/27/2017 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 09/27/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Specify the exhaust fan shown in the new storage room. Include the required airflow for the fan (e.g. 100 CFM @ 0.5" WG). State how the fan is to be controled. |
| 09/27/2017 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/27/2017 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Can not exit from a lower hazard through a higher hazard. Please recalculate travel distance from southeast corner of building to legal exit. |
| 09/27/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Written comments to architect. |
| 09/27/2017 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/27/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide secondary roof drainage. |
| 10/03/2017 | QJONES1 | ENGINEERING | REVIEW | Needs Review | |
| 10/03/2017 | QJONES1 | ZONING | REVIEW | Needs Review |