Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM07390
Parcel: 110163590

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T17CM07390
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2017 MMORENO1 ZONING REVIEW Approved
09/27/2017 ENEWCOM1 ADA REVIEW Passed
09/27/2017 ENEWCOM1 FIRE REVIEW Needs Review
09/27/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
09/27/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
09/27/2017 PAUL BAUGHMAN ENGINEERING REVIEW Needs Review The depreciated value online does not provide enough capacity to provide for designating this as a non substantial improvement given the $71,438.78 valuation listed on the permit. Applicant will need to provide an updated appraisal of the existing structure to show that the value of the improvements do not exceed 50% of the value of the existing structure. Alternatively, the applicant will need to show that the site is not subject to the 100 year flood or that it is elevated at least a foot above the 100 year flood if it is subject to the 100 year floodplain.

A Floodplain use permit will be required unless hydraulic analysis demonstrates otherwise.