Permit Number: T17CM07318
Parcel: 11822041A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T17CM07318
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2017 ALEXANDRA HINES ZONING REVIEW Approved
11/01/2017 AHINES2 ENGINEERING REVIEW Passed
11/01/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
11/01/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/02/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Natural ventilation is not the same as mechanical ventilation. [Initial comment: Provide mechanical ventilation for the apartments. Reference: Section R403.5, IECC 2012.]
11/02/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Coordinate the route of the water service to the building with the architect; see sheet AS1.]
2. Comment not resolved. Structural detail 22/S1.3 does not accommodate the weight of the 50-gallon water heater and there is no design for the platform. [Initial comment: Provide structural calculations for the installation of the 50-gallon water heaters to show that the supporting walls are structurally sound. Note that detail 8/P3 calls out wood studs but the walls are built with metal studs. Reference: Section 307.1, IPC 2012.]
3. The riser diagram (3/P3) and the 1st floor plumbing plan do not clearly show the 3" drop from the 2nd floor running horizontally for 10 pipe diameters before connecting to a horizontal drain on the 1st floor. [Initial comment: Horizontal branches shall connect no closer than ten diameters downstream of the bases of vertical stacks (see 3/P3). Reference: Section 704.3, IPC 2012.]
11/02/2017 ROBERT SHERRY WATER REVIEW Reqs Change Comment not addressed. [Initial comment: Clarify the number and size of the water meters serving this building. The previous activity, T15CM01898, showed a ¾" meter (located approximately where the current P1 drawing shows a 1" meter) and a new 1" meter (located near the northeast corner of the property).]