Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM07318
Parcel: 11822041A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07318
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2017 ROBERT SHERRY WATER REVIEW Reqs Change Clarify the number and size of the water meters serving this building. The previous activity, T15CM01898 showed a ¾" meter (located approximately where the current P1 drawing shows a 1" meter) and a new 1" meter (located near the northeast corner of the property).
09/28/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Coordinate the route of the water service to the building with the architect; see sheet AS1.
2. If the proposed 1" water meter serves the six new apartments and the existing five apartments, revise the water demand calculations accordingly.
3. The water heater schedule shows four units but six are shown on the plans: coordinate the plans.
4. Provide structural calculations for the installation of the 50-gallon water heaters to show that the supporting walls are structurally sound. Note that detail 8/P3 calls out wood studs but the walls are built with metal studs. Reference: Section 307.1, IPC 2012.
5. Horizontal branches shall connect no closer than ten diameters downstream of the bases of vertical stacks (see 3/P3). Reference: Section 704.3, IPC 2012.
09/28/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide energy code compliance calculations for the alterations to the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and NFRC-rated U-factors of the fenestration components, along with the R-values of the insulation and the NFRC-rated SHGC for the fenestration. Reference: Sections R101.4.3, R101.5, R103.2, and R401.2, International Energy Conservation Code 2012.
2. Provide mechanical ventilation for the apartments. Reference: Section R403.5, IECC 2012.
3. Provide thermal load and HVAC equipment-sizing calculations to confirm the specified heat pumps for each apartment type. Reference: Section R403.6, IECC 2012.
10/02/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheets C1, C1.1, AS1, A1 & A2: Drawings were sealed by the registrant on 9/8/2017 but an expiration date of 6/30/17 is denoted. Verify and revise.
2. Sheet C1: On the drawings, include calculations for the minimum number of units required to be Accessible, Type A and Type B.
3. Sheet A1 & A2: Plans indicate the new units are to be Type B. On drawings, reference code section(s) which will allow the use of spiral stairs in a Type B dwelling unit.
4. Sheet A2: On the drawings, include a building section/detail which clearly illustrates continuity of the fire partitions. Reference IBC Section 708.4
5. Sheet A2 Detail 3: On the drawings, indicate the size, type and number of fasteners to be used for the attachment of ceiling joists to wall studs.
6. Sheet S1.0 Epoxy in Concrete: Hilti HIT-RE 500-SD Epoxy report 2322 is no longer valid. Please reference a current report.
7. Sheet S1.0 Epoxy in Masonry: Hilti HY-150 Report 5193 is no longer valid. Please reference a current report.
8. Sheet S1.0 Expansion Bolts in Concrete: Simpson Strong Bolt Report 1771 is no longer valid. Please reference a current report.
9. Sheet S1.0 Post Installed Anchors: Item 10 Special Inspections references the 2006 IBC. Please reference the 2012 IBC as adopted by the City of Tucson.
10. General Structural: Provide a Special Inspection Certificate for all required Special Inspections.
11. General: Provide written responses to all comments.
10/13/2017 MARTIN BROWN FIRE REVIEW Approved
10/19/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide smoke detectors in all the areas required per 2012 IBC sec, 907. See electrical floor plans.
#2. Why is panel 'Z' schedule shown on Plan Sheet E-3? How does it correlate with this project? Why is it not shown on the one lines?
#3. The branch circuit designations shown on the power plans do not correlate with the panel schedules.
#4. Panel schedule identified as "NQ". Should that be "N"?
#5. Plan Sheet E-1, Note #7, Refers to IRC. Please revise to NEC. Any multifamily over two units is addressed as Commercial, therefore the 2011 NEC would be the applicable code for electrical.
#6. Ref: Plan Sheet E-4. What does "Load CLS" mean on the panel schedules? Please fill in the blanks (loads) on the panel schedules.
#7. Provide for Tamper Resistant Receptacles as required per NEC art, 404.12, NEC 210.
#8. Provide for Arc Fault branch circuit protection as required per NEC art, 210.12.
#9. Provide full compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting.
Ref: 2012 IBC sec, 107.2.1, 2011 NEC
10/20/2017 QJONES1 ENGINEERING REVIEW Needs Review
10/20/2017 QJONES1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2017 QJONES1 APPROVAL SHELF Completed
10/20/2017 QJONES1 OUT TO CUSTOMER Completed
10/20/2017 QJONES1 REJECT SHELF Completed