Permit Number: T17CM07270
Parcel: 11808094P

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T17CM07270
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide a site plan and a building floor plan to show how the proposed work relates to the existing situation. Refernce: Section 107.2.1, IBC 2012.
2. Show the source of the hot water and verify that the source is not over 50-feet from the load.
3. Show how the pipes are protected from freezing.