Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T17CM07244
Parcel: 126211070

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T17CM07244
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2017 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T17CM07244
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray or rigid board tight to the roof sheathing), R806.5. This condensation control provision is necessary for code compliance, and may be a single layer of air-impermeable insulation, or layered with batt insulation for achieving the total required roof R-value. Update keynote #14/A3 & A4.

PLUMBING PLANS:

1. Show hot water pipe with minimum R-3 insulation, N1103.4.2.
2. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Update the gas line diagram and table for showing the BTU demand and length of line to the proposed outdoor kitchen.

MECHANICAL PLANS:

1. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical system calculations may be provided by deferred submittal. The deferred calculations must be approved through revision process prior to mechanical inspections.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
10/19/2017 JVINCEN1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/23/2017 KROBLES1 OUT TO CUSTOMER Completed