Permit Number: T17CM07170
Parcel: 141220290

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T17CM07170
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2017 MCASTRO2 ZONING REVIEW Approved
09/19/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/19/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Assign a branch circuit as well as a panel designation for all electrical equipment, receptacles, and lighting.
#2. Provide a complete panel schedule, include load calcs.
Ref; 2012 IBC sec, 107.2.1, 2011 NEC art 408. City of Tucson Commercial Plan
Submittal Requirements.
09/19/2017 MCASTRO2 ENGINEERING REVIEW Passed
09/19/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/19/2017 ROBERT SHERRY WATER REVIEW Completed
09/19/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/19/2017 JVINCEN1 FIRE REVIEW Approved
09/19/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed