Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T17CM07152
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/23/2017 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Calculations have been provided for support of the water heater but no design has been shown on the drawings. [Initial comment: Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported from the building structure. Reference: Section 301.2, IPC 2012.] 2. Verify that the manufacturer's listing allows the installation of an expansion tank on the hot water supply piping. [Initial comment: Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503, 504, 606.1, and 607.3, IPC 2012.] 3. No cleanout has been shown for the section of the building drain located immediately downstream of the hydromechanical grease interceptor. [Initial comment: Provide a cleanout for the section of the building drain located immediately downstream of the hydromechanical grease interceptor. Reference: Section 708.3.1 and 708.3.3, IPC 2012.] 4. The specified hydromechanical grease interceptor (Schier GB-25) has a built-in flow control device. The additional flow control fitting and vent shown in the grease interceptor piping detail is not needed. |
| 10/23/2017 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |