Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2017 MMORENO1 ZONING REVIEW Approved
09/18/2017 MMORENO1 ENGINEERING REVIEW Passed
09/19/2017 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
09/19/2017 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
09/19/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G1.1 (Project Data); Sheet AD1.0 (Project Data): The data on G1.1 indicates B occupancy, while data on AD1.0 indicates retail. Please coordinate.
2. Sheet G1.1 (Project Data); Sheet AD1.0 (Project Data): The square footage listed on G1.1 indicates 805 SF, while the square footage listed on AD1.0 indicates 706 SF. Please coordinate.
3. Sheet G1.1 (Project Data); Sheet AD1.0 (Project Data): The occupant load listed on G1.1 indicates 4, while the occupant load listed on AD1.0 indicates 19. Please coordinate.
4. Sheet G1.3: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise. The notes are difficult to read.
5. Sheet A5.1; Detail A1: Please provide new stud sizes for the diagonal bracing. In addition, indicate the size and number of connectors for the bracing to the top of the partition and to the structure above. If horizontal bracing is used, include brace swize and connectors as required.
6. General: Please provide written responses to all review comments.
09/19/2017 JVINCEN1 FIRE REVIEW Approved
09/19/2017 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
09/19/2017 ROBERT SHERRY WATER REVIEW Completed
09/19/2017 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed