Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T17CM07130
Parcel: 12514021F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T17CM07130
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2017 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T17CM07130 - PLAN REVIEW COMMENTS
Reviewer: Chris Anderson, September 27, 2017
BUILDING – RESIDENTIAL
Revise the wall/footing configuration of wall section 6/A1.0 to match detail S.1/S1.0 so that stucco system is located past the face of foundation. This allows the stucco weep screed to be located per Code “at or below the foundation plate line.” Ref. 2012 IRC R703.6.2.1.
Add note to wall section 6/A1.0. “locate stucco weep screed at or below the foundation plate line and minimum 4” above ground surface and minimum 2” above paved surface.” Ref. 2012 IRC R703.6.2.1.
Change note on wall section 6/A1.0 so that roof insulation is located between new structural members rather than existing structural members. Ref. 2012 IRC R106.1.1.
Show landings at exterior doors on floor plan 2/A1.0 that are minimum 36” deep x width of door. Ref. 2012 IRC R311.3.
At windows on exterior elevations 3, 4 and 5/A1.0 add “maximum SHGC 0.25.” Ref. 2012 IRC Table N1102.1.1.
Since there is no windows schedule in the drawing set, add note on the window elevations that windows frames are to be metal with thermal break to comply with the Manual J and COMcheck. Ref. 2012 IRC R106.1.1.
There are conflicts between the building envelope components shown on the architectural plans, the COMcheck and the Manual J construction descriptions. All three sources of information must match each other. For example, the Manual S and architectural drawings only show R-21 insulation for the exterior walls; however the COMcheck shows R-21 cavity insulation plus R-5 continuous board insulation. And, the U-factors for windows is 0.40 on the architectural drawings, 0.69 and 0.56 in the Manual J and 0.33 in the COMcheck. Go through each item and revise documents to complement each other. Ref. 2012 IRC R106.1.1.
There are both metal framed, thermally broken windows and vinyl framed windows in the COMcheck. Is this correct?
The second copy of sheet A1.0 in the drawing set should be deleted since various items have been revised to comply with Code. Ref. 2012 IRC R106.1.1.
Add “*not used” to detail S.2 C-1/S1.0. Ref. 2012 IRC R106.1.1.
09/28/2017 FRODRIG2 WATER REVIEW Approved PER PIMA COUNTRY - CHRIS ANDERSON
09/28/2017 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – RESIDENTIAL
Indicate site utilites for this dwelling on the site plan, sheet A0.0. Show existing sewer, water and electric service runs, water meter location and size and water service pipe size. Show locations of connections for new lines to existing. Ref. 2012 IRC R106.1.1.
Delete note “plumber to verify existing meter size and locations. Size pipe accordingly” on sheet P1.0. This information must be a part of this permit drawing set. Ref. 2012 IRC R106.1.1.
09/28/2017 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – RESIDENTIAL
Show circuits on the electrical plan, sheet E1.0. Ref. 2012 IRC R106.1.1.
The electric load calculations incorrectly add the initial load to the adjusted loads. Revise as follows: 16,840 + 14,000 = 30,840 VA /240 V = 128.5 A. Unless desired for other reasons, a 150 A or 200 A main breaker will suffice.
Exterior light fixtures shall be full cutoff type or submit outdoor lighting lumen calculations for the entire site showing compliance with the 2012 Outdoor Lighting Code.
On Main Panel Schedule, sheet E1.0 indicate which circuits are GFCI and which circuits are AFCI. Ref. 2012 IRC R106.1.1.
09/28/2017 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANICAL – RESIDENTIAL
No duct sizes nor cooling CFMs are shown on the mechanical plan, sheet M1.0. Provide a Manual D and revise the mechanical plan to show the calculated duct sizes and supply air CFM’s. CFM’s on the plan must be within 10% of the CFM’s calculated by the Manual D. Ref. 2012 IRC R106.1.1.
Revise the Manual J per Building comment 7 above and, as follows: 1) change the “construction quality” from “average” to “tight” or “semi-tight” since this is a new building, 2) change the “rate/swing multiplier” for sensible cooling equipment load sizing from “1.10” to “1.00.” 1.10 will artificially add approximately 10% to the sensible load. Resize the mechanical unit if necessary based on the revised Manual J and modify the mechanical unit specification note on sheet M1.0.
Identify the thermostat in the equipment schedule, sheet M1.0, as capable of controlling the heating and cooling system on a daily schedule to maintain different set points at different times of day. Ref. 2012 IRC N1103.1.1.
A whole house ventilation system is required. Either provide one bathroom fan a minimum of 30 CFM programmed to run continuously or provide controls for the mechanical heating and cooling unit to have that fan run continuously. Ref. 2012 IRC M1507.3.
Provide exhaust for the kitchen range. Ref. 2012 IRC M1503.1 and Table M1507.4.