Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T17CM07054
Parcel: 124071390

Address:
55 N PARK AV

Review Status: Active

Review Details: REVISION - - 2ND

Permit Number - T17CM07054
Review Name: REVISION - - 2ND
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also, provide a written response. This submittal shows added equipment not shown in the first submittal, some items per request of the plan reviewer. This generated additional comments.
#1. Please provide load calcs in the panel schedules.
, and balance phases.
#2. The grounding electrode conductors for the transformers are under sized, should be #2 cu. NEC 250.30A(5).
#3. The neutral is to be bonded 1 time only at the service. The line diagram shows them bonded at the ses, and the 400 amp disconnects. Neutrals can be bonded at either locations but not both. NEC 250.24.
Ref; 2011 NEC, 2012 IBC 107.2.1