Permit Review Detail
Review Status: Active
Review Details: REVISION - - 2ND
Permit Number - T17CM07054
Review Name: REVISION - - 2ND
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/28/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also, provide a written response. This submittal shows added equipment not shown in the first submittal, some items per request of the plan reviewer. This generated additional comments. #1. Please provide load calcs in the panel schedules. , and balance phases. #2. The grounding electrode conductors for the transformers are under sized, should be #2 cu. NEC 250.30A(5). #3. The neutral is to be bonded 1 time only at the service. The line diagram shows them bonded at the ses, and the 400 amp disconnects. Neutrals can be bonded at either locations but not both. NEC 250.24. Ref; 2011 NEC, 2012 IBC 107.2.1 |