Permit Number: T17CM07054
Parcel: 124071390

Address:
55 N PARK AV

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T17CM07054
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide a site plan showing the locations of all electrical equipment.
#2. Provide complete panel schedules for 'HT' and 'LT'.
#3. Show all OCPD's in the main service.
#4. Provide for disconnecting means for the elevator and the crane as required per NEC 430.
Ref; 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements (electrical) www.tucsonaz.gov/pdsd.