| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/15/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide a site plan showing the locations of all electrical equipment. #2. Provide complete panel schedules for 'HT' and 'LT'. #3. Show all OCPD's in the main service. #4. Provide for disconnecting means for the elevator and the crane as required per NEC 430. Ref; 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements (electrical) www.tucsonaz.gov/pdsd. |