Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2017 MARTIN BROWN FIRE REVIEW Approved
10/11/2017 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G0.3; Site Plan: Please provide a new site plan that clearly indicates the separation distance between the larger shade structure and the western smaller shade structure. In addition, clearly indicate the separation distance between the two smaller shade structures.
2. Sheet G0.3; Site Plan: Per the IBC Table 602, the fire separation distance between the new structure and the property line must be at least 10'-0", or a fire resistance rating will be required for the structure. The distance from the larger shade structure to the north property line is indicated as 7'-6". Please verify and revise the location as required, or provide a fire resistance rated structure.
3. Sheet S1 (12' x 12' canopy); Structural Calculations: The calculations indicate a 5/32" diameter cable, while the drawing indicates a 1/8" diameter cable. Please coordinate.
4. Structural Calculations (16' x 16' Canopy); Sheet S1: Please provide full sized sheets (match the site plan Sheet G0.3) so the notes and dimensions will meet the minimum height requirement of 3/32". This will provide clearly legible drawings when archived.
5. Structural Calculations (12' x 12' Canopy); Sheet S1: Please provide full sized sheets (match the site plan Sheet G0.3) so the notes and dimensions will meet the minimum height requirement of 3/32". This will provide clearly legible drawings when archived.
6. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2017 KROBLES1 OUT TO CUSTOMER Completed