Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T17CM07001
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/25/2017 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/11/2017 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G0.3; Site Plan: Please provide a new site plan that clearly indicates the separation distance between the larger shade structure and the western smaller shade structure. In addition, clearly indicate the separation distance between the two smaller shade structures. 2. Sheet G0.3; Site Plan: Per the IBC Table 602, the fire separation distance between the new structure and the property line must be at least 10'-0", or a fire resistance rating will be required for the structure. The distance from the larger shade structure to the north property line is indicated as 7'-6". Please verify and revise the location as required, or provide a fire resistance rated structure. 3. Sheet S1 (12' x 12' canopy); Structural Calculations: The calculations indicate a 5/32" diameter cable, while the drawing indicates a 1/8" diameter cable. Please coordinate. 4. Structural Calculations (16' x 16' Canopy); Sheet S1: Please provide full sized sheets (match the site plan Sheet G0.3) so the notes and dimensions will meet the minimum height requirement of 3/32". This will provide clearly legible drawings when archived. 5. Structural Calculations (12' x 12' Canopy); Sheet S1: Please provide full sized sheets (match the site plan Sheet G0.3) so the notes and dimensions will meet the minimum height requirement of 3/32". This will provide clearly legible drawings when archived. 6. General: Please provide written responses to all review comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/11/2017 | KROBLES1 | OUT TO CUSTOMER | Completed |